|
|
Technical Information
Earthing
The various standards for earthing provide design limits to be met and
together with codes of practice explain how the earthing system can be
designed to meet these. There are differences in the design limits
applying to consumer installations and to supply industry installations
and reference should be made to the correct standard to check the limits
which apply in each situation.
In the past it was normal practice to design an earthing system to
achieve a certain impedance value. The earth electrodes being positioned
near the equipment where a fault current was expected to pass. Recently,
this has changed towards the approach used in North America. The most
important difference is that the earthing system is designed to ensure
that potentials in its vicinity are below appropriate limits. These
potentials are referred to as:
i) Step Potential (the potential difference between two points on the
surface of the soil which are 1m apart).
ii) Touch Potential (the potential difference during fault conditions
between exposed metalwork and a point on the soil surface).
iii) Transfer Potential (the potential difference between an insulated
cable connected to a remote earth reference and the earth rod).
A number of factors will determine whether or not a person experiencing
any of these potentials will be at risk, and the standards attempt to
take these into account to ascertain the limits below which the design
will be considered acceptable. The ultimate risk, of course, being that
the potentials are high enough to cause a fatal electric shock.
Lightning Protection
If an unprotected building were to be struck by lightning the result may
be fire, structural damage, damage to the electrical systems/equipment
and electric shock. The purpose of a lightning protection scheme is to
shield a building, its occupants and contents from these adverse
effects.
To do this properly the lightning protection system must capture the
lightning, lead it safely down to earth, and disperse the energy within
the ground. Whether or not a building needs a lightning protection
scheme depends on several factors. . .
The Code of Practice for Protection of Structures against Lightning
details and these are used to estimate risk. The risk assessment takes
into account the following factors:
Soil Resitivity, the external dimensions of the structure including any
adjacent structures that are electrically connected. The flash density
(in thunderstorm days per year) for the area. The type of construction.
Height above sea level and proximity of other structure such as tall
trees. The length of any overhead cables entering the structure.
In the ensuing calculation, if the risk is found to be less than
1:100,000 then no protection is generally required. However this needs
to be assessed in relation to the consequences of a direct strike. For
instance, if the building is an explosive store then the highest level
of protection will be required even if the risk of a strike is low.
Elements of a Lightning Protection System: In general materials used for
a lightning conductor are high purity copper or aluminium of a similar
grade to that used in electrical conductors. These low impedance
materials are required to ensure that the lightning energy will flow
safely to the ground.
The principal parts are detailed below. Air Termination: This is made up
of vertical air terminals and/ or a lattice of conductors on the roof
and edges of the structure. Since no part of the roof should be more
than 5m from the nearest horizontal conductor, a 10m x 20m lattice is
generally
used on large buildings. Traditional taper-pointed air terminals are not
as frequently used today but when they are they should be positioned
near those points where a strike is most likely to hit the building.
Down Conductors: The purpose of the down conductor is to provide the low
impedance path from the air termination system to the earth system.
There is typically one down conductor for every 20m or part thereof the
building perimeter at roof or ground level. If the building is above 20m
in height or of an abnormal risk this distance should be reduced to 10m.
Any good conductor which forms part of the building structure can be
employed as a down conductor with appropriate connection to the air
termination and earthing systems. For down leads not part of the
structure, copper and aluminium are the most widely used materials.
These are sometimes PVC sheathed for aesthetic purposes only. Where
practical they should be routed directly from the air termination to the
earth system and be spaced symmetrically around the outside walls of the
structure.
At all times consideration must be given to the possibility of side
flashing. Each down conductor should also be provided with a test point
as a means of isolating the earth electrode for test purposes.
Earth Termination: Each down conductor must have its own earth electrode
termination and the resistance to earth of the whole system must not be
greater than 10 Ohms without taking into account bonding to other
services. The most common terminations are rods driven into the ground.
These should be a minimum of 9m for the whole system.
The individual earth electrodes are sometimes interconnected by a ‘ring
conductor’ to help reduce the overall resistance. This should be at
least 0.6m below ground level and preferably pass below incoming
services. The ring conductor is made from copper tape or cable
(aluminium is not permitted for use below ground) and also helps to
provide potential equalisation at ground level, in addition to potential
grading.
The earth system should be designed as a whole since the complete
installation should rise in potential together, to avoid excessive
voltage differences. For this reason, the earth termination should be
bonded to the rest of the earth electrodes.
Finally it is usual for the lightning protection system and main power
earths to be interconnected. However, where this is not desirable for
technical reasons, an earth potential equaliser can be installed between
them. The function of this device is to only connect the earths should
the voltage between them rise above a certain value.
Bonding: An important element in the design of a lightning protection
system is the consideration of bonding of exposed metalwork on or near
the structure. This is to ensure that side flashing does not occur.
If exposed metalwork such as pipes or ducts etc. were not bonded to the
system then, when a current flows in the down conductor creating a
potential, the metalwork could be initially at a potential nearer that
of earth. There would therefore be a potential difference between them.
If this potential difference was greater than the breakdown value of the
air or material in between, then a side flash could occur resulting in
severe damage.
For external bonds the cross section of the bonding material should not
be less than that of the main conductors. Internal bonds can however be
of smaller cross section since they are mainly for equipotential
purposes and are unlikely to carry a proportion of the lightning
current.

Manufacturing To Customer Satisfaction
Using the combination of machinery and skilled staff, Kingsmill can in
cases produce bespoke products. When an enquiry is made, it is usual for
a drawing to be provided for the customer and confirmed with our
engineering staff that the potential job is feasible. In some cases,
advice is provided where necessary to the customer on the feasibility of
certain jobs, or general advice on how the product would be best
manufactured.

This helps to ensure that the customer is completely satisfied with the
product that will be manufactured for them which enables to create an
efficient delivery time and ensure that there is complete cohesion with
the customer. All products are designed and manufactured to meet British
& International standards including BS EN 62305, BS EN 50164 and BS7430.
|
|